1
PV500-44U 06/12
INSTALLATION & MAINTENANCE MANUAL
POWER VT
PLUS WATER HEATER
MODELS (40, 50, 75, 90, 100) LX 125 A-PVIF
MODELS (50, 75, 90, 100) LX (250, 300) A-PVIF
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, OPERATION AND
MAINTENANCE OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER
PROVIDED INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS UNIT.
TO THE INSTALLER: After installation, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain
important information that will help you in maintaining and operating this appliance.
PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com - Phone 1-800-433-5654
Vue de la page 0
1 2 3 4 5 6 ... 41 42

Résumé du contenu

Page 1 - PLUS WATER HEATER

1 PV500-44U 06/12INSTALLATION & MAINTENANCE MANUAL POWER VT PLUS WATER HEATER MODELS (40, 50, 75, 90, 100) LX 125 A-PVIF MODELS (50, 75, 90, 10

Page 2

10 PV500-44U 06/124 WATER HEATER INSTALLATION 4.1 Checking Equipment Before You Install Inspect the unit completely upon receipt from the freig

Page 3

11 PV500-44U 06/128. Do not install on carpet or other combustible floor coverings. If installation over a combustible floor is required, follow th

Page 4 - PRODUCT SAFETY INFORMATION

12 PV500-44U 06/12 SINGLE WATER PIPING SINGLE STORAGE WATER HEATER WITH SUPPLEMENTAL STORAGE TANK

Page 5 - IMPORTANT SAFETY NOTE

13 PV500-44U 06/12 TWO WATER HEATERS WITH REVERSE RETURN PIPING 6 CONDENSATE DRAIN, TRAP & DISPOSAL The POWER VT PLUS water heater is desig

Page 6

14 PV500-44U 06/12 Condensate Piping and Trap with Optional Condensate Neutralizer 6.1 Condensate Neutralization System (optional) Although only

Page 7

15 PV500-44U 06/127 GAS SUPPLY AND PIPING Verify that the type of gas specified on rating plate is supplied to the unit. This unit is orificed for

Page 8

16 PV500-44U 06/12Use this corrected total distance from the meter for determining the suggested pipe size in the “Single Unit Installation Suggeste

Page 9

17 PV500-44U 06/127.7 Gas Connection 1. Safe operation of unit requires adequate gas supply with the required static and dynamic (flow) pressures.

Page 10

18 PV500-44U 06/128.2 Maximum Allowed Remote Combustion Air Inlet Length (Equivalent Length) A vertical or horizontal remote air inlet system can

Page 11

19 PV500-44U 06/12 Vertical Remote Air Horizontal Remote Air 8.5 Remote Air Consideration for Combined Remote Air Ducting Each water heater MUS

Page 12

2 PV500-44U 06/12 TABLE OF CONTENTS 1. Safety Considerations 2. Standard Features and Equipment 2.1 Performance 2.2 Pressure Vessel 2.3 Heat Ex

Page 13

20 PV500-44U 06/12WARNING: Do not vent this water heater into an existing or traditional gas vent or chimney or combine the vent with any other appl

Page 14

21 PV500-44U 06/124. Dry-fit a solid 6” CPVC pipe into the female economizer flue outlet. Remove the pipe and apply a liberal coating of room tempe

Page 15

22 PV500-44U 06/1210. A vertical termination less than 10 feet (0.91 m) from a parapet wall must be a minimum of 2 feet (0.61 m) higher than the pa

Page 16

23 PV500-44U 06/1210.2 Operating Temperature Control An adjustable digital operating control is located in the front control panel. The control is

Page 17

24 PV500-44U 06/1211 TEMPTRAC™ ELECTRONIC CONTROLLER PANEL 11.1 Principle Of Operation The water heater operates to satisfy the setpoint of the

Page 18

25 PV500-44U 06/1211.5 To View The Setpoint  Push and release the SET key to see the set point value.  To return to normal display, press SET

Page 19

26 PV500-44U 06/1211.8 LED Display Alarm Messages Alarm messages are displayed in the upper LED readout and alternate with the default display. An

Page 20

27 PV500-44U 06/1212.2 The Following Describes The Functions Of Each Of These Terminals And The Factory-Installed Options Required To Activate The

Page 21

28 PV500-44U 06/124. Proof of Air Pressure Switch - The control will look for a signal from the airflow-proving switch, indicating that the blower

Page 22

29 PV500-44U 06/1214 INITIAL STARTUP 14.1 Initial Startup Requirements Installation should be complete prior to performing initial startup; and t

Page 23

3 PV500-44U 06/1210. Operating and Safety Controls 10.1 Temperature and Pressure Relief Valve(s) 10.2 Operating Temperature Control 10.3 Hi

Page 24

30 PV500-44U 06/12b. Attach a manometer to measure the gas pressure at the manual gas shutoff valve located just upstream of the gas train. Adjust

Page 25

31 PV500-44U 06/1219. When the blower motor starts, the flame control will check for a positive air flow. If the air switch or blocked filter switc

Page 26

32 PV500-44U 06/12 Gas Train Illustration for Models 40 through 50 (Optional components may not be shown) Gas Train Illustration for Mode

Page 27

33 PV500-44U 06/1215 TROUBLESHOOTING GUIDE Problem Probable Cause Corrective Action Starting or Pre-purge Failure Power Supply Check fuse and/o

Page 28

34 PV500-44U 06/1216 REPLACEMENT PARTS REPLACEMENT PARTS

Page 29

35 PV500-44U 06/1216.1 Control Panel

Page 30

36 PV500-44U 06/1216.2 Control Panel Components (Optional components may not be included) Key No. Part No. Description Qty. U/M 1 101947 CONTR

Page 31

37 PV500-44U 06/1216.3 Burner Assembly Optional components may or may not be shown

Page 32

38 PV500-44U 06/1216.4 Burner Assembly Components (Optional components may not be included) Item No. Qty. PVI Part No. Description 1 1 111876

Page 33

39 PV500-44U 06/1217 PERIODIC MAINTENANCE Listed below are items that must be checked to ensure safe reliable operations. Maintenance must be perfor

Page 34 - 16 REPLACEMENT PARTS

4 PV500-44U 06/121 SAFETY CONSIDERATIONS WARNING: If the information in the supplied manual(s) is not followed exactly, a fire, explosion or exp

Page 35

40 PV500-44U 06/12i. Cycle unit and test to verify all safety and operating controls are properly functioning and the burner top plate flange is fr

Page 36

41 PV500-44U 06/1218 RECOMMENDED MAINTENANCE SCHEDULE 1. Annual Maintenance a. Check all joints and pipe connections for tightness, corrosion or d

Page 37

42 PV500-44U 06/12PVI INDUSTRIES®, LLC  3209 Galvez Ave.  Fort Worth, Texas 76111  Phone 1-800-433-5654  www.pvi.com

Page 38

5 PV500-44U 06/12 IMPORTANT SAFETY NOTE It takes only 5 seconds of skin contact with 140°F water to cause a second degree burn! You must protect

Page 39

6 PV500-44U 06/122 STANDARD FEATURES AND EQUIPMENT 2.1 Performance  98% thermal efficiency at full fire from 40° to 140°F  Up to 99% thermal e

Page 40

7 PV500-44U 06/123 PRODUCT DESCRIPTION Component, Controls and Connection Locations (Locations May Vary) 125 SERIES

Page 41

8 PV500-44U 06/12250 SERIES

Page 42 - PVI INDUSTRIES

9 PV500-44U 06/12300 SERIES